1 手术室高效空气过滤器经外观检查合格后,应立即进行安装;
 
1 operation room, high efficiency air filter through the appearance inspection, should be immediately installed;
 
2 安装高效过滤器的框架应平整、清洁,每台过滤器的安装框架的平整度偏差,不得超过1~2㎜;
 
2 installation and high efficiency filter framework should be smooth, clean, and every filter mounting frame flatness deviations, shall not exceed 1 ~ 2 mm;
 
3 过滤器安装方向必须正确,安装后过滤器四周和接口,应严密不漏;
 
3 filter must be installed in the direction of the right, after the installation of the filter around and interface, should be strict no leakage;
 
4 高效过滤器采用机械密封时,应采用气密垫密封,其厚度为6~8㎜,并紧贴在过滤器边框上;安装后垫料的压缩应均匀,压缩率为25~50%;安装后应进行扫描检漏;
 
4, filter adopts mechanical seal, a sealing gasket, the thickness of 6-8 mm, and close to the filter frame; after installation gasket compression should be uniform, compression rate of 250%; after installation should be scans leak;
 
5 高效过滤器采用液压密封时,槽架安装水平,并不得有渗漏现象;槽内无污物和水分。槽内密封液高度宜为槽深的2/3,密封液的熔点宜高于50℃。
 
5 high efficiency filter adopts hydraulic seal, the slot bracket installation level, and can not have leakage phenomenon; the groove without dirt and moisture. The height of sealing fluid in the tank should be 2/3, and the melting point of the sealing fluid should be higher than 50.